G60RS | Rental Set – JCB Power Products Diesel Generator Data Sheet Summary Overview
Model: G60RS Rental Set
Type: Diesel generator, Stage IIIA compliant
Configuration: 3-phase canopy-enclosed rental set
Rated speed: 1500 RPM (50 Hz primary); 1800 RPM data shown as N/A
Dimensions & Weight:
- Length: 3334 mm
- Width: 1200 mm
- Height: 1912 mm
- Shipping volume (sea ready): 7.70 m³
- Weight (with all fluids except fuel): 2045 kg
Electrical Ratings (ISO 8528 reference conditions):
- Frequency: 50 Hz
- Phases: 3
- Voltage: 400/230 V
- Prime power: 60 kVA / 48 kW
- Standby power: 66 kVA / 53 kW
- MCB Rating: 100 A
- Minimum ATP Rating: 100 A
- Rated speed: 1500 RPM
- Power factor: 0.8 (3-phase)
- Maximum load impact: 40 kVA / 32 kW
Engine:
- Manufacturer/Model: JCB 448 G-TC 60
- Net Output Rating (PRP) 1500 RPM: 54 kW
- Net Output Rating (Standby) 1500 RPM: 56 kW
- Fuel: Diesel
- Injection: Direct
- Aspiration: Turbo Charged
- Cylinders: 4
- Bore × Stroke: 103 × 135 mm
- Displacement: 4.77 L
- Cooling: Water
- Engine oil specification: API CH4
- Compression ratio: 18 : 1
- Engine oil capacity: 15.00 L
- Coolant capacity: 16.00 L
- Governor: Mechanical
- Air filter: Two stage Paper Element
- Engine oil consumption (100% load): 0.1% of fuel consumed
Alternator (ECP32-2M4 B):
- Poles: 4
- Winding connections: Star
- Insulation: Class H
- Enclosure: IP23
- Exciter system: Self-regulating brushless
- Voltage regulator: AVR
- Steady state voltage regulation: ±1%
- Bearing: Single bearing sealed
- Coupling: Flexible disc
- Cooling: Direct drive centrifugal blower fan
- Coating: Total Protection +
Starting System:
- Starter motor: 4.20 kW
- Battery capacity: 120 Ah
- Number of batteries: 1
- Auxiliary voltage: 12 V
Fuel System:
- Diesel specification: EN590
- Standard capacity fuel tank: 280 L (Standard)
- Extended capacity fuel tank (Option): 560 L
Fuel Consumption (50 Hz):
- 100% Load Prime: 15 L/h
- 75% Load Prime: 11.9 L/h
- 50% Load Prime: 8.20 L/h
- 100% Load Standby: 15.50 L/h
Exhaust System:
- Maximum temperature (100% Standby): 511.00 °C
- Exhaust gas flow (100% Standby): 13.43 m³/min
- Maximum allowed back pressure: 9.00 kPa
- Exhaust discharge size: 80 mm
Sound Pressure:
- LpA (7 m) at 50 Hz: 67 dB(A)
Canopy Features:
- Lockable Maintenance Access Doors
- Control Panel Viewing Window
- Oversized Fork Pockets
- Welded Single Lift Point
- Bunding
- Certified 4 Point Lift
- High Density Fire Retardant Foam
- Yellow Paint
- Heavy Duty Rental Base
- Galvanised Steel Canopy
Mechanical Features:
Standard (?)
- Cooling Pack
- Air Filter
- Mechanical Governor
- Low Oil Pressure Switch
- Coolant Temperature Sender
- Oil Temperature Sender
- Radiator Guards
- Hot Component Guards
- Pre-Filter with Separator
- Fuel Level Sender
- Internal Fuel Fill (Belly Tank)
- 3 Way Fuel Valve
- Residential Silencer
- Manual Oil Drain Pump (Canopy)
- Water Jacket Heater
Optional (?)
- Air Shut-Off Valve
- Spark Arrestor
Electrical Features:
Standard (?)
- AVR DSR
- Winding Protection Total +
- MAUX
- Earth Leakage Protection (Switchable)
- Preparation for Earth Spike
- Emergency Stop Button (Control Panel)
- External Emergency Stop Button
- AGM Battery
- 4 Pole Moulded Case Circuit Breaker
- Winding Protection Total
- Bund Alarm / Shut down
Optional (?)
- PMG
- Anti-Condensation Heater
- Optional Voltages
- Socket Panel (1 × 63A – 3ph, 3 × 32A – 1ph) IP44
- Remote Display
- Socket Panel (1 × 63A – 3ph, 2 × 32A – 3ph, 3 × 32A – 1ph) IP44 / (1 × 125A – 3ph) IP67
- AVR DER
Battery Features:
- Battery Isolator
- Battery Type: SEALED LEAD ACID
- Battery Size: 120 Ah
- Number of Batteries: 1
- Battery Charger
JCB Communication and Control:
Standard (?)
- DSE 7320 MKII
- JCB Livelink (Optional - Enquiry at PR Power)
Optional (?)
- 8610 MKII (Synchronisation - Enquiry at Pr Power)
- 8620 (Synchronisation - Enquiry at Pr Power)
CE Pack:
Standard (?)
- EMC Certification
- Hot Guards
- Belt Guards
- Sound Power Decal
- EU Declaration for Engine Emissions
- Complete Machine Declaration of Conformity
Reference Standards:
- CE certified and conforms to the following Directives (subject to country requirements):
- EN 12100, EN 13857, EN 60204
- 2006/42/CE Machinery safety
- 2006/95/EC Low voltage
- 2004/108/EC Electromagnetic compatibility
- 2000/14/EC Sound Power Level (amended by 2005/88/EC)
- 97/68/EC Emissions (amended by 2002/88/EC & 2004/26/EC)
- Power according to ISO 8528 and ISO 3046
- Ambient reference conditions: 1000 mbar, 25 °C, 30% relative humidity (ISO 3046)