505-13 Diesel Fire Booster Pumpset
Diesel Fire Booster Pumpset to AS2941-2013
Duty: 20 l/s 250m head + 130%l/s 80%m
One (1) only Aline model PMS80H/7A end suction horizontal multistage pump with ductile cast iron casing, zinc free bronze
impeller, direct flexibly coupled to a 80kW 2,500rpm heat exchanger cooled diesel engine on a fabricated galvanized steel
baseplate. Fitted to unit shall be a diesel control panel, bunded fuel tank, instruments, muffler, flexible connector and
interconnecting wiring.
Power Requirements: 240 volts, 1.5kW & 15 amps
One Aline CRIEkW 415 volt automatic pressure maintenance pump capable of 40l/min 230 m, complete with
pressure transducer, pressure gauge and pressure vessel mounted on a galvanized steel baseplate and wired to dedicated
control panel. Jacking pump shall be fully pre-piped with check valve and isolating valves fitted as required.
Power Requirements: 415 volts, 4kW & 8 amps on a dedicated circuit
Supply unit fully piped with 100mm gear operated butterfly valve and grooved end check valve on pump discharge. Suction
fitted with 100mm OS&Y gate valve.
- Starting and control batteries.
- Water jacket heater on diesel engine.
- Mounts for bases